Amendment Number One

 

to the

  

Red River Authority of Texas

Clean River Program

Quality Assurance Project Plan

 FY 2004 – FY 2005

 

 

Prepared in Cooperation with the

Texas Commission on Environmental Quality

Under the Authorization of the Texas Clean Rivers Act

 

 

Clean Rivers Program

Technical Analysis Division

Texas Commission on Environmental Quality

P.O. Box 13087, MC - 147

Austin, Texas 78711-3087

 

 

 

Questions concerning this QAPP should be directed to:

 

Curtis W. Campbell, General Manager

Red River Authority of Texas

Hamilton Building, Suite 520

900 Eighth Street

Wichita Falls, Texas 76301-6894

(940) 723-8697

Fax (940) 723-8531

 

 

 

 

 

 

Amended February 2004

 

Justification: This document details the modification made to the basin-wide Quality Assurance Project Plan to update Table A7.1, Measurement Performance Specifications, to reflect additional EPA methods used in laboratory analyses by the Red River Authority of Texas Regional Laboratory and to update certain parameters and EPA methods performed by the CRMWA and LCRA laboratories.

 

Summary of Changes: The following information in Amendment I is amended to add the following changes:

 

•          Revision of Table A7.1 – Measurement Performance Specifications

 

•          Addition of Chemical Water Analysis and E. Coli Bacteria Log Forms to QAPP Appendices

 

Detail of Changes: The addition of Red River Authority’s Regional Laboratory conducting analysis of Chlorophyll a and Pheophytin by EPA Method 446.0; the analysis of Ortho Phosphate-P, Nitrite-N, Nitrate-N, Sulfate, Chloride, and Fluoride by EPA method 300.0; and the analysis of Ammonia-N by EPA method 350.3. In addition, Fecal Coliform will be added back to Table A7.1 and Total Hardness, Storet Codes 00900 and 82394 will be removed from the table for RRA. Also included in the update of TableA7.1 is the addition of EPA method 300.0 for the analysis of Ortho Phosphate-P, Nitrate-N, Sulfate, and Chloride, and Fluoride by the storet code 00950 has been removed from the table for the Canadian River Municipal Water Authority (CRMWA) Laboratory. In addition SM 9223-B for the analysis of E. coli by CRMWA has been added. A change in the EPA method number for Nitrite/Nitrate-N from 353.3 to 353.2 and changes to the method numbers for Chlorophyll a and Pheophytin to EPA Method 446.0, with a back-up method of SM 10200H, as performed by the Lower Colorado River Authority laboratory has also been made to Table A7.1. In addition, a newly developed storet code of 20424 has been added for Water Clarity to Table A7.1 under Field Parameters. Additionally, Chemical Water Analysis and E. coli Bacteria Log forms to be submitted by CRMWA have been added to Appendix C (see attached).

 

These changes will be incorporated into the Quality Assurance Project Plan for the Red and Canadian River Basins for FY 2004 – FY 2005. The Texas Commission on Environmental Quality and the Red River Authority of Texas will acknowledge and accept these changes by signing this amendment.

 

 

_______________________________________________                        ___________________

Curtis W. Campbell, RRA Project Manager                                                                             Date

 

 

_______________________________________________                        ___________________

David L. Holub, RRA Quality Assurance Officer                                                                      Date

 

 

_______________________________________________                        ___________________

Laurie Curra, CRP Project Manager                                                                                        Date

 

 

_______________________________________________                        ___________________

CRP Lead Quality Assurance Specialist                                                                                    Date

 

 

_______________________________________________                        ___________________

Laurie Curra, CRP Project Quality Assurance Specialist                                                           Date

 

 

 

Table A7.1 - Measurement Performance Specifications

PARAMETER

UNITS

MATRIX

METHOD

STORET

AWRL

LAB

REPORTING

LIMIT (RL)

RECOVERY AT RLS

PRECISION

(RPD OF LCS

/ LCS DUPS)

BIAS

%REC. OF LCS

LAB

Field Parameters

Conductivity

uS/cm

Water

EPA 120.1,

TCEQ SOP

00094

NA*

NA

NA

NA

NA

Field

Days Since Last

Significant Rain

Days

NA

TCEQ SOP

72053

NA*

NA

NA

NA

NA

Field

DO

mg/L

Water

EPA 360.1,

TCEQ SOP

00300

NA*

NA

NA

NA

NA

Field

Flow Measurement Method

1 - gage

2 - electric

3 - mechanical

4 - weir/flume

Water

TCEQ SOP

89835

NA*

NA

NA

NA

NA

Field

Flow

Estimate

cfs

Water

TCEQ SOP

74069

NA*

NA

NA

NA

NA

Field

Flow

cfs

Water

TCEQ SOP

00061

NA*

NA

NA

NA

NA

Field

Flow

Severity

1 - no flow

2 - low

3 - normal

4 - flood

5 - high

6 - dry

Water

TCEQ SOP

01351

NA*

NA

NA

NA

NA

Field

pH

pH/units

Water

EPA 150.1, TCEQ SOP

00400

NA*

NA

NA

NA

NA

Field

Present

Weather

1 - clear

2 - ptly cloudy

3 - cloudy

4 - rain

NA

NA

89966

NA

NA

NA

NA

NA

Field

Salinity

ppt,

marine only

Water

SM 2520,

TCEQ SOP

00480

NA*

NA

NA

NA

NA

Field

Secchi Depth

meters

Water

TCEQ SOP

00078

NA*

NA

NA

NA

NA

Field

Temperature

C

Water

EPA 170.1,

TCEQ SOP

00010

NA*

NA

NA

NA

NA

Field

Turbidity

NTU

Water

SM 2130-B

82079

.5

.5

75-125

20

80-120

Field

Water

Odor

1 - sewage

2 - chemical

3 - rotten egg

4 - musky

5 - fishy

6 - none

7 - other

NA

NA

89971

NA

NA

NA

NA

NA

Field

Water

Clarity

1 - excellent

2 - good

3 - fair

4 - poor

NA

NA

20424

NA

NA

NA

NA

NA

Field

Water

Color

1 - brownish

2 - reddish

3 - greenish

4 - blackish

5 - clear

6 - other

NA

NA

89969

NA

NA

NA

NA

NA

Field

Conventional and Bacteriological Parameters

Ammonia-N, Total

mg/L

Water

EPA 350.1

00610

.02

.02

75-125

20

80-120

RRA

Ammonia-N, Total

mg/L

Water

EPA 350.3

00610

.02

.02

75-125

20

80-120

RRA

Chloride

mg/L

Water

EPA 300.0

00940

10

10

75-125

20

80-120

CRMWA

Chloride

mg/L

Water

EPA 300.0

00940

10

10

75-125

20

80-120

RRA

Chlorophyll-a, Fluorometric Method

ug/L

Water

SM 10200-H

70953

5

5

 75-125

20

NA

LCRA

Chlorophyll-a, Spectrophoto-metric Method

ug/L

Water

EPA 446.0

32211

5

5

 75-125

20

NA

RRA

Chlorophyll-a, Spectrophoto-metric Method

ug/L

Water

EPA 446.0

32211

5

2

 75-125

20

NA

LCRA

E. coli, IDEXX Colilert

MPN/100 mL

Water

SM 9223-B

31699

1

1

NA

.5 **

NA

CRMWA

E. coli, IDEXX Colilert

MPN/100 mL

Water

SM 9223-B

31699

1

1

NA

.5 **

NA

RRA

Fecal Coliform

cfu / 100 mL

Water

SM 9222-D

31616

1

1

NA

.5 **

NA

RRA

Fluoride, Total

mg/L

Water

EPA 300.0

00951

.5

.5

75-125

20

80-120

CRMWA

Fluoride, Total

mg/L

Water

EPA 300.0

00951

.5

.5

75-125

20

80-120

RRA

Pheophytin, Fluorometric Method

ug/L

Water

SM 10200-H

32213

3

3

NA

20

NA

LCRA

Pheophytin, Spectrophoto-metric Method

ug/L

Water

EPA 446.0

32218

3

2

NA

20

NA

LCRA

Pheophytin, Spectrophoto-metric Method

ug/L

Water

EPA 446.0

32218

3

3

NA

20

NA

RRA

Sulfate

mg/L

Water

EPA 300.0

00945

10

10

75-125

20

80-120

RRA

Sulfate

mg/L

Water

EPA 300.0

00945

10

10

75-125

20

80-120

CRMWA

TDS,

Calculated

mg/L

Water

Calculation

70294

NA

NA

NA

NA

NA

RRA

TDS, Dried at 180 Degrees C

mg/L

Water

EPA 160.1

70300

10

10

 NA

 

20

NA

RRA

TSS

mg/L

Water

EPA 160.2

00530

4

4

 NA

 

20

NA

RRA

Field, Conventional and Bacteriological Parameters; Non-TSWQS Metals

Alkalinity, Total

mg/L

Water

EPA 310.1

00410

10

10

NA

20

80-120

RRA

Alkalinity, Total

mg/L

Water

EPA 310.1

00410

10

10

NA

20

80-120

CRMWA

Calcium, Total

mg/L

Water

EPA 215.2

00916

.5

.5

75-125

20

80-120

RRA

COD

mg/L

Water

EPA 410.2

00335

10

10

75-125

20

80-120

RRA

Magnesium, Dissolved

mg/L

Water

SM 3500-Mg-B

00925

0.5

0.5

75-125

20

75-125

CRMWA

Nitrate/Nitrite-N, Total

mg/L

Water

EPA 353.2

00630

.04

.04

75-125

20

80-120

LCRA

Nitrate-N

mg/L

Water

EPA 300.0

00620

.02

.02

75-125

20

80-120

CRMWA

Nitrate-N

mg/L

Water

EPA 300.0

00620

.02

.02

75-125

20

80-120

RRA

Nitrite-N

mg/L

Water

EPA 300.0

00615

.02

.02

75-125

20

80-120

CRMWA

Nitrite-N

mg/L

Water

EPA 300.0

00615

.02

.02

75-125

20

80-120

RRA

Ortho Phosphate-P, Field Filtered

mg/L

Water

EPA 300.0

00671

.04

.04

75-125

20

80-120

RRA

Ortho Phosphate-P, Field Filtered

mg/L

Water

EPA 300.0

00671

.04

.04

75-125

20

80-120

CRMWA

Ortho Phosphate-P,

Field Filtered

mg/L

Water

EPA 365.3

 

00671

.04

.04

75-125

20

80-120

RRA

TOC

mg/L

Water

SM 5310-B

00680

2.0

2.0

75-125

20

80-120

RRA

Total Phosphorus-P

mg/L

Water

EPA 365.3

00665

.06

.06

75-125

20

80-120

RRA

VSS

mg/L

Water

EPA 160.4

00535

4

4

NA

20

80-120

RRA

 

*              Reporting to be consistent with SWQM guidance and based on measurement capability.

**            Based on a range statistic as described in Standard Methods, 20th Edition, 1998, Section 9020-B, “Quality Assurance/Quality Control - Intra laboratory Quality Control Guidelines. This criterion applies to bacteriological duplicates with concentrations >10 org./100mL.

 

References for Table A7.1:    United States Environmental Protection Agency (USEPA) “Methods for Chemical Analysis of Water and Wastes,” Manual #EPA-600/4-79-020 American Public Health Association (APHA), American Water Works Association (AWWA), and Water Environment Federation (WEF), “Standard Method for the Examination of Water and Wastewater,” 20th Edition, 1998.

 

TCEQ SOP:                             Surface Water Quality Monitoring Procedures Manual, most recent version. American Society for Testing and Materials (ASTM) Annual Book of Standards, Vol. 11.02

 

 

 

 

APPENDIX C

 

 

FIELD DATA SHEETS

 

 

CANADIAN RIVER MUNICIPAL WATER AUTHORITY

CHEMICAL WATER ANALYSIS FORM

 

 

 

Station/Sample Location

 

 

 

 

 

 

 

Date Sample Collected:

 

 

 

 

 

Sample Caught At (Time):

 

 

 

 

 

Air Temp: (˚F)

 

 

 

 

 

Wind Speed: (mph)

 

 

 

 

 

Wind Direction:

 

 

 

 

 

Ph (Standard Units)

 

 

 

 

 

Specific Conductance (µμs/cm)

 

 

 

 

 

Water Temperature: (oC)

 

 

 

 

 

P. Alkalinity

 

 

 

 

 

T. Alkalinity

 

 

 

 

 

Fluoride

 

 

 

 

 

Chloride

 

 

 

 

 

Nitrate (as N)

 

 

 

 

 

Phosphate

 

 

 

 

 

Sulfate

 

 

 

 

 

Sodium

 

 

 

 

 

Potassium

 

 

 

 

 

Calcium

 

 

 

 

 

Magnesium

 

 

 

 

 

Total Hardness

 

 

 

 

 

Latitude N

 

 

 

 

 

Longitude W

 

 

 

 

 

Water Color

 

 

 

 

 

 

(1-brown 2-red 3-green 4-black 5-clear 6-other*)

Water Odor (1-Sewage 2-oily/chem

 

 

 

 

 

 

3-rottin eggs 4-musky 5-fishy 6-none 7-other*)

Weather

 

 

 

 

 

 

(1-clear 2-partly cloudy 3-cloudy 4-rain)

Water Clarity

 

 

 

 

 

 

(1-excellent 2-good 3-fair 4-poor 5-other*)

Flow (CFS):

 

 

 

 

 

Collected By:

 

 

 

 

 

Analyzed By:

 

 

 

 

 

Date Analyzed:

 

 

 

 

 

Sample Depth:

 

 

 

 

 

Lake Depth:

 

 

 

 

 

All values given as parts per million with the exception of pH and Specific Conductance.

ND = Not Detected

 

 

 

 

 

*** Value taken in field

 

 

 

 

 

*Comments:

 

 

 

CANADIAN RIVER MUNICIPAL WATER AUTHORITY

 

 

E. Coli BACTERIA LOG

 

Exp. Date of Media:

Collector(s):

 

Date on:

Time on:

 

Start Temp: (oC)

 

 

 

 

Sample Location

 

Sample ID No.

 

mL Used

 

Dilution Factor

 

E. coli

 

Small Cells

Large Cells

MPN/ mL

 

1

 

 

100

None

 

 

 

 

2

 

 

100

None

 

 

 

 

3

 

 

100

None

 

 

 

 

4

 

 

100

None

 

 

 

 

5

 

 

100

None

 

 

 

 

6

 

 

100

None

 

 

 

 

7

 

 

100

None

 

 

 

 

8

 

 

100

None

 

 

 

 

9

 

 

100

None

 

 

 

 

10

 

 

100

None

 

 

 

 

11

 

 

100

None

 

 

 

 

12

 

 

100

None

 

 

 

 

13

 

 

100

None

 

 

 

 

14

 

 

100

None

 

 

 

 

15

 

 

100

None

 

 

 

 

16

 

 

100

None

 

 

 

 

17

 

 

100

None

 

 

 

 

18

 

 

100

None

 

 

 

 

19

 

 

100

None

 

 

 

 

20

 

 

100

None

 

 

 

 

Date off:

Time off:

End Temp: (oC)

 

Method Used to Determine Counts: E. coli Idexx MPN Chart

 

Comments: